Piping and instrumentation diagram

From The Right Wiki
Jump to navigationJump to search

A Piping and Instrumentation Diagram (P&ID or PID) is a detailed diagram in the process industry which shows process equipment together with the instrumentation and control devices. It is also called as mechanical flow diagram (MFD).[1] Superordinate to the P&ID is the process flow diagram (PFD) which indicates the more general flow of plant processes and the relationship between major equipment of a plant facility.

Contents and function

File:Industrial control loop.jpg
Example of a single industrial control loop; showing continuously modulated control of process flow.
File:Pump with tank pid en.svg
Piping and instrumentation diagram of pump with storage tank. Symbols according to EN ISO 10628 and EN 62424.
File:P&ID.JPG
A more complex example of a P&ID.

A piping and instrumentation diagram (P&ID) is defined as follows:

  1. A diagram which shows the interconnection of process equipment and the instrumentation used to control the process. In the process industry, a standard set of symbols is used to prepare drawings of processes. The instrument symbols used in these drawings are generally based on International Society of Automation (ISA) Standard S5.1
  2. The primary schematic drawing used for laying out a process control installation.

They usually contain the following information:

  • Mechanical equipment, including:
  • Process piping, sizes and identification, including:
    • Pipe classes and piping line numbers
    • Flow directions
    • Interconnections references
    • Permanent start-up, flush and bypass lines
    • Pipelines and flowlines
    • Blinds and spectacle blinds
    • Insulation and heat tracing
  • Process control instrumentation and designation (names, numbers, unique tag identifiers), including:
    • Valves and their types and identifications (e.g. isolation, shutoff, relief and safety valves, valve interlocks)
    • Control inputs and outputs (sensors and final elements, interlocks)
    • Miscellaneous - vents, drains, flanges, special fittings, sampling lines, reducers and swages
  • Interfaces for class changes
  • Computer control system
  • Identification of components and subsystems delivered by others

P&IDs are originally drawn up at the design stage from a combination of process flow sheet data, the mechanical process equipment design, and the instrumentation engineering design. During the design stage, the diagram also provides the basis for the development of system control schemes, allowing for further safety and operational investigations, such as a Hazard and operability study (HAZOP). To do this, it is critical to demonstrate the physical sequence of equipment and systems, as well as how these systems connect. P&IDs also play a significant role in the maintenance and modification of the process after initial build. Modifications are red-penned onto the diagrams and are vital records of the current plant design. They are also vital in enabling development of;

  • Control and shutdown schemes
  • Safety and regulatory requirements
  • Start-up sequences
  • Operational understanding.

P&IDs form the basis for the live mimic diagrams displayed on graphical user interfaces of large industrial control systems such as SCADA and distributed control systems.

Identification and reference designation

Based on STANDARD ANSI/ISA S5.1 and ISO 14617-6, the P&ID is used for the identification of measurements within the process. The identifications consist of up to 5 letters. The first identification letter is for the measured value, the second is a modifier, 3rd indicates passive/readout function, 4th - active/output function, and the 5th is the function modifier. This is followed by loop number, which is unique to that loop. For instance FIC045 means it is the Flow Indicating Controller in control loop 045. This is also known as the "tag" identifier of the field device, which is normally given to the location and function of the instrument. The same loop may have FT045 - which is the flow transmitter in the same loop.

Letter Column 1
(Measured value)
Column 2
(Modifier)
Column 3
(Readout/passive function)
Column 4
(Output/active function)
Column 5
(Function modifier)
A Analysis Alarm
B Burner, combustion User choice User choice User choice
C User's choice (usually conductivity) Control Close
D User's choice (usually density) Difference Deviation
E Voltage Sensor
F Flow rate Ratio
G User's choice (usually gaging/gauging) Gas Glass/gauge/viewing
H Hand High
I Current Indicate
J Power Scan
K Time, time schedule Time rate of change Control station
L Level Light Low
M User's choice Middle / intermediate
N User's choice (usually torque) User choice User choice User choice
O User's choice Orifice Open
P Pressure Point/test connection
Q Quantity Totalize/integrate Totalize/integrate
R Radiation Record Run
S Speed, frequency Safety (Non SIS (S5.1)) Switch Stop
T Temperature Transmit
U Multivariable Multifunction Multifunction
V Vibration, mechanical analysis Valve or damper
W Weight, force Well or probe
X User's choice (usually on-off valve as XV) X-axis Accessory devices, unclassified Unclassified Unclassified
Y Event, state, presence Y-axis Auxiliary devices
Z Position, dimension Z-axis or Safety Instrumented System Actuator, driver or unclassified final control element

For reference designation of any equipment in industrial systems the standard IEC 61346 (Industrial systems, installations and equipment and industrial products — Structuring principles and reference designations) can be applied. For the function Measurement the reference designator B is used, followed by the above listed letter for the measured variable. For reference designation of any equipment in a power station the KKS Power Plant Classification System can be applied.

Symbols of chemical apparatus and equipment

Below are listed some symbols of chemical apparatus and equipment normally used in a P&ID, according to ISO 10628 and ISO 14617.

Symbols of chemical apparatus and equipment
File:Pipe.svg
Pipe
File:Insulated pipe.svg
Thermally insulated pipe
File:Jacketed pipe.svg
Jacketed pipe
File:Cooled or heated pipe.svg
Cooled or heated pipe
File:Flexible pipe.svg
Flexible connection
File:Symbol Hydro pump.svg
Hydraulic pump
File:Pump.svg
Pump
File:Vacuum Pump or Compressor.svg
Vacuum pump or compressor
File:Fan.svg
Fan
File:Axial fan.svg
Axial fan
File:Radial fan.svg
Radial fan
File:Dryer.svg
Dryer
File:Autoclave.svg
Jacketed mixing vessel (autoclave)
File:Half pipe reactor.svg
Half pipe mixing vessel
File:Pressurized vessel horizontal.svg
Pressurized horizontal vessel
File:Pressurized vessel vertical.svg
Pressurized vertical vessel
File:Fluid contacting column.svg
Packed column
File:Tray column.svg
Plate column
File:Furnace.svg
Furnace
File:Cooling tower.svg
Cooling tower
File:Heat exchanger with cross.svg
Heat exchanger
File:Heat exchanger no cross.svg
Coil heat exchanger
File:Cooler-symbol.svg
Cooler
File:Plate heat exchanger.svg
Plate & frame heat exchanger
File:Double pipe heat exchanger.svg
Double pipe heat exchanger
File:Fixed straight tubes heat exchanger.svg
Fixed straight tubes heat exchanger
File:U shaped tubes heat exchanger.svg
U-shaped tubes heat exchanger
File:Spiral heat exchanger symbol.svg
Spiral heat exchanger
File:Covered gas vent.svg
Covered gas vent
File:Curved gas vent.svg
Curved gas vent
File:Dust trap.svg
Air filter
File:Funnel.svg
Funnel or tundish
File:Steam trap.svg
Steam trap
File:Viewing glass.svg
Viewing glass
File:Pressure reducing valve.svg
Pressure reducing valve
File:Valve.svg
Valve
File:Gate valve.svg
Gate valve
File:Control valve.svg
Control valve
File:Manual valve.svg
Manual valve
File:Back draft damper.svg
Check valve
File:Needle valve.svg
Needle valve
File:Butterfly valve.svg
Butterfly valve
File:Diaphragm valve.svg
Diaphragm valve
File:Ball valve.svg
Ball valve
File:Check Valve.svg
Check valve
File:Back draft damper.svg
Back draft damper
File:Bag.svg
Bag
File:Gas bottle.svg
Gas bottle
Globe valve Globe valve Valve3 3-way valve P&ID Piston Compressor Symbol Piston or reciprocating compressor Spring safety valve Relief valve
Rupture disc Turboexpander Centrifugal pump Reciprocating pump

Historical use

Prior to the advent of computer-aided design (CAD) in the late 1980s, P&IDs were drawn by hand. The drawing template shown below, actual size 225.mm by 111 mm, is typical of those used to draw P&IDs.

File:P&ID drawing template.jpg

Piping and instrumentation diagram manual drawing template (1980s). Symbol key:

  1. Vessel dished end
  2. Motor driven pump or compressor and baseplate
  3. Valves
  4. Valve diaphragm actuator
  5. Shell and tube heat exchanger
  6. Flexible hose, bellows
  7. Ejector
  8. Machine driven pump or other device
  9. Reducers

See also

External links

References

  1. Turton, Richard; Bailie, Richard C.; Whiting, Wallace B.; Shaeiwitz, Joseph A.; Bhattacharyya, Debangsu (2012). Analysis, synthesis, and design of chemical processes. Prentice Hall international series in the physical and chemical engineering sciences (4th ed.). Upper Saddle River, N.J. Munich: Prentice Hall. ISBN 978-0-13-261812-0.